Chilled water pipe supports
Calculate pipe, fluid and insulation mass, gravity loads, support quantities and CSV schedules.
Loads & quantities
Support schematic
Mass breakdown by pipe group
| Group · size · count | Pipe kg/m | Fluid kg/m | Insulation kg/m | Group kg/m |
|---|
Three component columns are per pipe; group mass includes quantity.
Current segment quantities
Saved water pipe support segments
Save each segment to the selected project. Reload to edit and update. Up to 300 segments; material totals appear in the schedule report.
Calculation basis & scope
Horizontal pipes of equal route length, full of fluid, under static gravity. Supports at both ends with equal bays no longer than requested spacing. N = ceil(L / s) + 1; actual spacing a = L / (N − 1). Interior support mass is q × a; with only 2 supports each takes q × L / 2. This is a tributary-length model, not a continuous-pipe analysis.
m = π/4 × (D² − d²) × ρ; d = D − 2t. D, d and t are in metres. Insulation uses the outer annular area. Load (kN) = (tributary mass + support own mass) × 9.80665 / 1000 + extra load.
Extra load is the combined additional concentrated load at the most loaded support; include valves, fittings, protective jackets and omitted components. Quantities exclude waste. Shared supports use 2 rods and 1 bearer per set; single-pipe hangers use 1 rod and no bearer. Each pipe has 1 clamp per support and 1 insulated insert if insulated.
Allowable spacing, pipe deflection, bearers, rods, anchors, thermal movement, seismic and test loads are not checked. Results are service loads without design factors. For chilled water, select load-bearing insulated inserts and maintain the vapour barrier to the product system; insert compression and condensation are not checked.
· Pipe sizing · Insulation check
Shared support layout: minimum rod span = insulated outside diameters + (pipe count − 1) × pipe gap + 2 × side clearance. Automatic span rounds up to 50 mm; cut length = span + 2 × end allowance. This checks geometric fit, not structural capacity. Legacy segments retain their entered bearer length; edit them to opt into automatic layout.
Results support preliminary calculations and require verification before use. View terms of use.