HVAC Studio / Duct fabrication & material take-off
DUCTWORK ENGINEERING

Duct fabrication & material take-off

Calculate duct material quantities and mass from editable example values or your own inputs. Guide →

Design inputs

1. Geometry & duct run
mm
mm
mm
m
m
2. Joints & stiffeners
m

Edit detailed parameters
kg/m
kg/m
3. Development & insulation
mm
kg/m³
%

Edit detailed parameters
mm
mm
kg/m
Pa

Results

Method & scope

Automatic mode updates thickness and joints when low-pressure rectangular galvanized duct dimensions change. Manual edits switch that setting to Manual. Combinations are starting values for material quantities, not pressure-capacity checks or mandatory construction.

All inputs start with editable example values. Section length and waste can be adjusted to match the sheet size and fabrication method. Pressure records the design condition and does not enter the take-off equations.

Straight, constant-section duct run only. Dimensions are outside the sheet-metal shell, excluding insulation. Density is the stated example material value; coating mass is not calculated separately.

Sections N = ceil(L/l); internal joints = N−1. Flanges use two frames per joint plus entered terminal frames. Slip joints/bands use one perimeter per joint and exclude terminal frames. Intermediate stiffeners restart in each fabricated section and exclude end frames.

Developed sheet area = mean perimeter × L + seam allowances + end allowances. Purchased sheet includes waste; installed mass excludes waste. For integral flanges, enter the actual end development and set additional flange mass to zero if already included in that sheet development.

Elbows, transitions, tees, access doors, dampers, bolts, corners, gaskets, sealant and nesting optimization are excluded. A joint name alone does not establish sheet/joint strength, leakage class or pressure capacity.

The integral-flange sample adds 30 mm/end and no separate flange mass. Sample section length is capped at 1.14 m for a 1.22 m sheet dimension with 20 mm cutting reserve. This is an operating example; use actual machine development and sheet dimensions. Quick joint/stiffener choices do not verify pressure capacity.