HVAC Studio / Tool guide

TOOL GUIDE

Duct fabrication & material take-off

Calculate duct material quantities and mass from editable example values or your own inputs.

Purpose & scope

Calculate duct material quantities and mass from editable example values or your own inputs.

The integral-flange sample adds 30 mm/end and no separate flange mass. Sample section length is capped at 1.14 m for a 1.22 m sheet dimension with 20 mm cutting reserve. This is an operating example; use actual machine development and sheet dimensions. Quick joint/stiffener choices do not verify pressure capacity.

Inputs

Use drawings, design conditions and manufacturer data. Units and example values follow the calculator; example values are not universal design requirements.

ParameterValue / interpretation
Duct shapeSelect the actual geometry, material or construction.
Sheet materialSelect the actual geometry, material or construction.
Outside width / outside diameter · mmAllowed input range: 50–5000 mm. Example values are not prescribed construction or capacities.
Outside height · mmAllowed input range: 50–5000 mm. Example values are not prescribed construction or capacities.
Thickness selectionSelect the actual geometry, material or construction.
Sheet thickness · mmAllowed input range: 0.3–5 mm. Example values are not prescribed construction or capacities.
Straight run length · mAllowed input range: 0.1–10000 m. Example values are not prescribed construction or capacities.
Maximum fabricated section length · mAllowed input range: 0.1–6 m. Example values are not prescribed construction or capacities.
Signed design static pressure · PaAllowed input range: -10000–10000 Pa. Example values are not prescribed construction or capacities.
Transverse joint selectionSelect the actual geometry, material or construction.
Quick joint setupSelect the actual geometry, material or construction.
Quick stiffener setupSelect the actual geometry, material or construction.
Transverse jointSelect the actual geometry, material or construction.
Terminal flange framesAllowed input range: 0–2 . Example values are not prescribed construction or capacities.
Flange / coupling mass per perimeter metre · kg/mAllowed input range: 0–20 kg/m. Example values are not prescribed construction or capacities.
Maximum intermediate stiffener spacing · mAllowed input range: 0.1–6 m. Example values are not prescribed construction or capacities.
Stiffener mass per perimeter metre · kg/mAllowed input range: 0–20 kg/m. Example values are not prescribed construction or capacities.
Quick external insulationSelect the actual geometry, material or construction.
Sheet allowance per longitudinal seam · mmAllowed input range: 0–100 mm. Example values are not prescribed construction or capacities.
Longitudinal seams per cross-sectionAllowed input range: 0–8 . Example values are not prescribed construction or capacities.
Sheet allowance at each section end · mmAllowed input range: 0–100 mm. Example values are not prescribed construction or capacities.
Sheet purchasing waste · %Allowed input range: 0–100 %. Example values are not prescribed construction or capacities.
External insulation thickness · mmAllowed input range: 0–300 mm. Example values are not prescribed construction or capacities.
Insulation density · kg/m³Allowed input range: 0–500 kg/m³. Example values are not prescribed construction or capacities.
Additional distributed mass · kg/mAllowed input range: 0–500 kg/m. Example values are not prescribed construction or capacities.

Steps

  1. Enter outside dimensions, material, thickness and run/section lengths. Inputs have example values to get started.
  2. Use ? for thickness suggestions and usable section length from sheet size. Choose joint, stiffener and insulation presets to fill their parameters. Open Edit detailed parameters to customize.
  3. Automatic mode updates thickness and flanges with size within the suggestion scope. Manual edits switch that setting to Manual. Name and save each segment in a project for a combined schedule report/PDF.
  4. Review quantities before/after waste, transfer installed mass to supports and save the project or export JSON.

Worked example

This reproducible training example uses the values below. Select the appropriate mode and overwrite restored project values. Example rates, K values and equipment losses are assumptions, not mandatory design criteria.

All example inputs
ParameterValue / interpretation
Duct shaperect
Sheet materialsteel
Outside width / outside diameter600 mm
Outside height400 mm
Thickness selectionauto
Sheet thickness0.8 mm
Straight run length12 m
Maximum fabricated section length1.2 m
Signed design static pressure500 Pa
Transverse joint selectionauto
Quick joint setupangle25
Quick stiffener setupnone
Transverse jointangle
Terminal flange frames2
Flange / coupling mass per perimeter metre1.10685 kg/m
Maximum intermediate stiffener spacing0.6 m
Stiffener mass per perimeter metre0 kg/m
Quick external insulation25-48
Sheet allowance per longitudinal seam30 mm
Longitudinal seams per cross-section2
Sheet allowance at each section end0 mm
Sheet purchasing waste10 %
External insulation thickness25 mm
Insulation density48 kg/m³
Additional distributed mass0 kg/m

Expected results (rounded)

ParameterValue / interpretation
Purchased sheet including waste27.15 m²
Installed mass229.51 kg
Internal connections9

Small differences in displayed rounding are normal. A result that passes the entered limits does not establish suitability for the complete system.

Method & limitations

The integral-flange sample adds 30 mm/end and no separate flange mass. Sample section length is capped at 1.14 m for a 1.22 m sheet dimension with 20 mm cutting reserve. This is an operating example; use actual machine development and sheet dimensions. Quick joint/stiffener choices do not verify pressure capacity.

Automatic mode updates thickness and joints when low-pressure rectangular galvanized duct dimensions change. Manual edits switch that setting to Manual. Combinations are starting values for material quantities, not pressure-capacity checks or mandatory construction.

All inputs start with editable example values. Section length and waste can be adjusted to match the sheet size and fabrication method. Pressure records the design condition and does not enter the take-off equations.

Straight, constant-section duct run only. Dimensions are outside the sheet-metal shell, excluding insulation. Density is the stated example material value; coating mass is not calculated separately.

Sections N = ceil(L/l); internal joints = N−1. Flanges use two frames per joint plus entered terminal frames. Slip joints/bands use one perimeter per joint and exclude terminal frames. Intermediate stiffeners restart in each fabricated section and exclude end frames.

Developed sheet area = mean perimeter × L + seam allowances + end allowances. Purchased sheet includes waste; installed mass excludes waste. For integral flanges, enter the actual end development and set additional flange mass to zero if already included in that sheet development.

Elbows, transitions, tees, access doors, dampers, bolts, corners, gaskets, sealant and nesting optimization are excluded. A joint name alone does not establish sheet/joint strength, leakage class or pressure capacity.

The integral-flange sample adds 30 mm/end and no separate flange mass. Sample section length is capped at 1.14 m for a 1.22 m sheet dimension with 20 mm cutting reserve. This is an operating example; use actual machine development and sheet dimensions. Quick joint/stiffener choices do not verify pressure capacity.

Common mistakes

Mixing outside/clear dimensions; treating example values as required construction; adding purchasing waste to hanger load; double counting integral flange sheet.

Projects & reports

  1. Choose or create an engineering project and enter your actual design inputs.
  2. Project inputs/results are autosaved in this browser. Where a saved-list panel is available, name and add the selected section or alternative to compare multiple options.
  3. Review the report before exporting PDF. In the print dialog select Save as PDF. Export JSON for backup and use Open file to restore it; PDF cannot restore project data.

Saved results do not automatically recalculate when another tool changes. Review any dependency warning, recalculate and update the affected results.

References & related tools

HVAC Studio — Duct sizing

The tool implements the methods and limits stated above; linking a standard does not establish complete compliance with that standard.