Select rods and bearers from trial loads, check each trapeze and save run schedules for reporting.

Purpose & scope

Select rods and bearers from trial loads, check each trapeze and save run schedules for reporting.

Example trapeze count = ceil(run length/spacing)+1, including both ends of each independent run. The entered spacing remains the conservative tributary length for checks. Bearer total is the rod-to-rod span only, excluding end extensions; rod totals exclude splices, nuts and embedment. Shared end supports across rows are not merged.

Inputs

Use drawings, design conditions and manufacturer data. Units and example values follow the calculator; example values are not universal design requirements.

ParameterValue / interpretation
Duct shapeSelect the actual geometry, material or construction.
Sheet materialSelect the actual geometry, material or construction.
Outside width / outside diameter · mmAllowed input range: 50–5000 mm. Example values are not prescribed construction or capacities.
Outside height · mmAllowed input range: 50–5000 mm. Example values are not prescribed construction or capacities.
Thickness selectionSelect the actual geometry, material or construction.
Sheet thickness · mmAllowed input range: 0.3–5 mm. Example values are not prescribed construction or capacities.
Insulation presetSelect the actual geometry, material or construction.
External insulation thickness · mmAllowed input range: 0–300 mm. Example values are not prescribed construction or capacities.
Insulation density · kg/m³Allowed input range: 0–500 kg/m³. Example values are not prescribed construction or capacities.
Additional distributed mass · kg/mAllowed input range: 0–500 kg/m. Example values are not prescribed construction or capacities.
Equivalent joint/stiffener mass · kg/mAllowed input range: 0–500 kg/m. Example values are not prescribed construction or capacities.
Additional point mass on this trapeze · kgAllowed input range: 0–1000 kg. Example values are not prescribed construction or capacities.
Straight run length · mAllowed input range: 0.1–10000 m. Example values are not prescribed construction or capacities.
Rod span selectionSelect the actual geometry, material or construction.
Longitudinal hanger spacing · mAllowed input range: 0.1–6 m. Example values are not prescribed construction or capacities.
Bearer span between rods · mAllowed input range: 0.1–6 m. Example values are not prescribed construction or capacities.
Metric coarse-thread rodSelect the actual geometry, material or construction.
Length of each rod · mAllowed input range: 0.05–10 m. Example values are not prescribed construction or capacities.
Bearer mass per metre · kg/mAllowed input range: 0–100 kg/m. Example values are not prescribed construction or capacities.
Clearance each side of insulated duct · mmAllowed input range: 0–500 mm. Example values are not prescribed construction or capacities.
Rod & bearer selectionSelect the actual geometry, material or construction.
Support calculation basisSelect the actual geometry, material or construction.
Bearer · depth verticalSelect the actual geometry, material or construction.
Yield-strength divisor (preliminary assumption)Allowed input range: 1.5–5 . Example values are not prescribed construction or capacities.
Section-property / allowable-value referenceRecord the source document and revision for traceability.
Rod property class / product referenceRecord the source document and revision for traceability.
Bearer section & installed orientationRecord the source document and revision for traceability.
Allowable rod tensile stress (0: unavailable) · MPaAllowed input range: 0–1000 MPa. Example values are not prescribed construction or capacities.
Bearer section modulus about bending axis (0: unavailable) · cm³Allowed input range: 0–1000 cm³. Example values are not prescribed construction or capacities.
Bearer second moment about bending axis (0: unavailable) · cm⁴Allowed input range: 0–10000 cm⁴. Example values are not prescribed construction or capacities.
Bearer elastic modulus · MPaAllowed input range: 10000–300000 MPa. Example values are not prescribed construction or capacities.
Allowable bending stress (0: unavailable) · MPaAllowed input range: 0–1000 MPa. Example values are not prescribed construction or capacities.
Anchor product, substrate & capacity referenceRecord the source document and revision for traceability.
Allowable tension per anchor (0: unavailable) · kNAllowed input range: 0–1000 kN. Example values are not prescribed construction or capacities.
Deflection limit L / divisorAllowed input range: 100–1000 . Example values are not prescribed construction or capacities.

Steps

  1. Enter outside dimensions for automatic thickness or override it manually, then select insulation. Retain thickness and joint/stiffener loads received from fabrication.
  2. Enter run length, hanger spacing and rod length. Span follows insulated width plus clearance; edit span for a manual value.
  3. Automatic mode screens rod/bearer choices against the load and preliminary assumptions. Use verified data for other sections and supply anchor data separately.
  4. Name and save each run to summarize trapezes and rod/bearer lengths in reports/PDF.

Worked example

This reproducible training example uses the values below. Select the appropriate mode and overwrite restored project values. Example rates, K values and equipment losses are assumptions, not mandatory design criteria.

All example inputs
ParameterValue / interpretation
Duct shaperect
Sheet materialsteel
Outside width / outside diameter600 mm
Outside height400 mm
Thickness selectionauto
Sheet thickness0.8 mm
Insulation preset25-48
External insulation thickness25 mm
Insulation density48 kg/m³
Additional distributed mass0 kg/m
Equivalent joint/stiffener mass2 kg/m
Additional point mass on this trapeze0 kg
Straight run length12 m
Rod span selectionauto
Longitudinal hanger spacing2.4 m
Bearer span between rods0.8 m
Metric coarse-thread rodM8
Length of each rod1 m
Bearer mass per metre2.3864 kg/m
Clearance each side of insulated duct75 mm
Rod & bearer selectionauto
Support calculation basispreliminary
Bearer · depth verticalrhs40
Yield-strength divisor (preliminary assumption)3
Section-property / allowable-value reference
Rod property class / product reference
Bearer section & installed orientation
Allowable rod tensile stress (0: unavailable)80 MPa
Bearer section modulus about bending axis (0: unavailable)3.6682666666666663 cm³
Bearer second moment about bending axis (0: unavailable)7.336533333333333 cm⁴
Bearer elastic modulus200000 MPa
Allowable bending stress (0: unavailable)78.33333333333333 MPa
Anchor product, substrate & capacity reference
Allowable tension per anchor (0: unavailable)0 kN
Deflection limit L / divisor250

Expected results (rounded)

ParameterValue / interpretation
Tension per rod/anchor0.21 kN
Rod tensile stress5.85 MPa
Bearer moment82.18 N·m
Minimum I for example deflection limit0.69 cm⁴

Small differences in displayed rounding are normal. A result that passes the entered limits does not establish suitability for the complete system.

Method & limitations

Example trapeze count = ceil(run length/spacing)+1, including both ends of each independent run. The entered spacing remains the conservative tributary length for checks. Bearer total is the rod-to-rod span only, excluding end extensions; rod totals exclude splices, nuts and embedment. Shared end supports across rows are not merged.

Automatic selection checks bearer bending/deflection and rod tension independently, trying candidates from small to large. The largest candidate must still be checked; anchors are not selected. Editing a rod/bearer or span switches that setting to Manual.

Automatic selection screens M8–M20 rods and RHS 40×40×2, 60×40×2, 80×40×2 for rod tension, bearer bending and deflection; it does not select anchors. Editing a rod/bearer or span switches that setting to Manual. Verified-data mode never replaces section properties.

Preliminary mode assumes class 4.6 rods (fy=240 MPa) and S235 RHS (fy=235 MPa). The default divisor 3 is a tool screening assumption, not a prescribed design factor under an applicable code. I=(b h³−bi hi³)/12; Z=I/(h/2); self-weight uses section area ×7850 kg/m³. Ideal sharp corners with h vertical; these are not actual product catalogue properties.

Two vertical rods, symmetric loading and a simply supported bearer. Duct load over one hanger spacing is conservatively represented as a centre point load, compared with a symmetric load spread over the duct width. Bearer self-weight is uniform; each rod self-weight adds to anchor tension.

Mmax = P L/4 + Wbearer L/8; centre deflection = P L³/(48 EI) + 5 Wbearer L³/(384 EI). Rod stress = R/As; bearer bending stress = M/Z. As is the metric coarse-thread tensile stress area, not the nominal circular area.

Entered limits must be compatible allowable values for the service-load basis, with suitable safety factors already included. Do not enter ultimate failure loads or unconverted design resistances. Without a reference/capacity value, requirements are shown without a passing verdict.

Angle/channel names alone do not establish capacity: I and Z must match the bending axis and installed orientation. Torsion, instability, perforations, rod–bearer connections, local shell bearing, round-duct saddles, anchor substrate, edge distances, anchor groups and supporting structure are not checked.

Static gravity loads only; seismic, wind, vibration, person loads, risers, cantilevers, fire/smoke-rated ducts and code-required hanger spacing are excluded. Entered spacing is a trial assumption, not a recommended maximum.

Example trapeze count = ceil(run length/spacing)+1, including both ends of each independent run. The entered spacing remains the conservative tributary length for checks. Bearer total is the rod-to-rod span only, excluding end extensions; rod totals exclude splices, nuts and embedment. Shared end supports across rows are not merged.

Common mistakes

Using nominal circular area instead of thread As; wrong I/Z units or axis; ultimate anchor load used as allowable; omitted self-weight/insulation/accessories; treating component checks as complete-system approval.

Projects & reports

  1. Choose or create an engineering project and enter your actual design inputs.
  2. Project inputs/results are autosaved in this browser. Where a saved-list panel is available, name and add the selected section or alternative to compare multiple options.
  3. Review the report before exporting PDF. In the print dialog select Save as PDF. Export JSON for backup and use Open file to restore it; PDF cannot restore project data.

Saved results do not automatically recalculate when another tool changes. Review any dependency warning, recalculate and update the affected results.