TOOL GUIDE
Outdoor-air & AHU/FAHU cooling duty
Calculate mixed air, sensible/latent coil duty, condensate and chilled-water flow for a specified leaving-coil state.
Purpose & scope
Calculate mixed air, sensible/latent coil duty, condensate and chilled-water flow for a specified leaving-coil state.
Cooling/dehumidification above 0 °C only; no ADP/BF verification or coil selection. Condensate enthalpy, fan heat, recovery, reheat and pressure losses are excluded.
Inputs
Use drawings, design conditions and manufacturer data. Units and example values follow the calculator; example values are not universal design requirements.
| Parameter | Value / interpretation |
|---|---|
| System mode | Select the material/system appropriate to the actual application; verify reference values. |
| Outdoor airflow at outdoor conditions · m³/h | Volumetric flow at the calculation location; check the selected unit. |
| Outdoor dry-bulb temperature · °C | Outdoor dry bulb before mixing/coil, at the same conditions as outdoor volumetric flow. |
| Outdoor relative humidity · % | Relative humidity of outdoor air, in %. |
| Return airflow at return conditions · m³/h | Return volume flow at return temperature/RH; used in AHU mode only. |
| Return-air dry-bulb temperature · °C | Return temperature entering the mixing box; ignored in FAHU mode. |
| Return-air relative humidity · % | Return RH, paired with the return flow and temperature. |
| Coil leaving dry-bulb temperature · °C | Target dry bulb immediately after the cooling coil, before reheat or fan heat. |
| Coil leaving relative humidity · % | Target leaving RH; not automatically derived from saturation or bypass factor. |
| Entering chilled-water temperature · °C | Entering pure-water temperature; must be below leaving-air temperature for positive cooling duty. |
| Water leaving − entering temperature difference · K | Water temperature rise through the coil, not air temperature difference; leaving water must be colder than entering air. |
| Atmospheric pressure · kPa | Local absolute atmospheric pressure for air properties. |
| Water specific heat capacity · kJ/(kg·K) | Pure-water specific heat in kJ/(kg·K); this model does not support glycol. |
| Coil duty allowance · % | Allowance applied to both sensible and latent loads. |
Steps
- Choose 100% outdoor-air FAHU or mixed-air AHU; enter pressure and each inlet flow at its own state.
- Enter outdoor temperature/RH, return-air conditions if used, and target coil-leaving state.
- Enter entering water temperature, water temperature rise, specific heat and allowance. Review actual/allowance duty, condensate and the two distinct water flows.
- Transfer results to ducts/fan/pump as needed; obtain coil pressure drops and equipment data from the manufacturer.
Worked example
This reproducible training example uses the values below. Select the appropriate mode and overwrite restored project values. Example rates, K values and equipment losses are assumptions, not mandatory design criteria.
All example inputs
| Parameter | Value / interpretation |
|---|---|
| System mode | FAHU — 100% outdoor air |
| Atmospheric pressure | 101.325 kPa |
| Outdoor airflow at outdoor conditions | 2,000 m³/h |
| Outdoor dry-bulb temperature | 35 °C |
| Outdoor relative humidity | 60 % |
| Return airflow at return conditions | 6,000 m³/h |
| Return-air dry-bulb temperature | 24 °C |
| Return-air relative humidity | 50 % |
| Coil leaving dry-bulb temperature | 12 °C |
| Coil leaving relative humidity | 95 % |
| Entering chilled-water temperature | 7 °C |
| Water leaving − entering temperature difference | 5 K |
| Water specific heat capacity | 4.186 kJ/(kg·K) |
| Coil duty allowance | 10 % |
Expected results (rounded)
| Parameter | Value / interpretation |
|---|---|
| Air-side total cooling duty | 35.22 kW |
| Sensible duty | 14.8 kW |
| Latent duty | 20.42 kW |
| Duty with allowance | 38.74 kW |
| Condensate | 29.13 kg/h |
| Water flow at actual duty | 6.06 m³/h |
| Water flow with allowance | 6.66 m³/h |
| Leaving airflow | 1,812.89 m³/h |
Small differences in displayed rounding are normal. A result that passes the entered limits does not establish suitability for the complete system.
Method & limitations
Cooling/dehumidification above 0 °C only; no ADP/BF verification or coil selection. Condensate enthalpy, fan heat, recovery, reheat and pressure losses are excluded.
Each volume flow is entered at its own temperature, RH and pressure. ṁda = Qv/(3600v); mixing conserves dry-air mass, moisture and enthalpy. Leaving volume flow can differ from total inlet volume because air properties change.
Total duty = ṁda(hM − hL). Sensible duty is defined as ṁda(1.006 + 1.86WM)(TM − TL); latent duty is the remainder. Condensate = ṁda(WM − WL) × 3600 kg/h. Leaving condensate enthalpy is neglected.
Chilled water: Qv,w = Q/(ρw cp,w ΔTw) × 3600. Actual-duty and allowance-duty flows are separate; allowance does not increase condensate for the specified air states. Pure water only; glycol is unsupported.
Leaving air is a user-specified target, not verified against ADP, bypass factor, coil rows or area. Reheat, fan heat, recovery, leakage, pressure losses, room loads and multizone ventilation efficiency are excluded. No AHU/FAHU product selection or standards-compliance determination.
Common mistakes
Confusing outdoor-condition flow with supply flow; double counting outdoor-air load; requesting heating/humidification; applying allowance to condensate; confusing allowance water flow with actual-state water flow.
Projects & reports
- Choose or create an engineering project and enter your actual design inputs.
- Project inputs/results are autosaved in this browser. Where a saved-list panel is available, name and add the selected section or alternative to compare multiple options.
- Review the report before exporting PDF. In the print dialog select Save as PDF. Export JSON for backup and use Open file to restore it; PDF cannot restore project data.
Saved results do not automatically recalculate when another tool changes. Review any dependency warning, recalculate and update the affected results.
References & related tools
The tool implements the methods and limits stated above; linking a standard does not establish complete compliance with that standard.