HVAC Studio / Tool guide

TOOL GUIDE

Cooling load → air / water flow

Convert cooling load into supply airflow from sensible load and water flow from total load.

Purpose & scope

Convert cooling load into supply airflow from sensible load and water flow from total load.

Simple energy balance; does not simulate coils, dehumidification, bypass or equipment selection.

Inputs

Use drawings, design conditions and manufacturer data. Units and example values follow the calculator; example values are not universal design requirements.

ParameterValue / interpretation
Total cooling loadTotal cooling load from a load calculation or design condition.
Capacity unitkW / BTU/h / TR (refrigeration ton)
Sensible heat ratio (SHR) · %SHR = sensible / total load. Use the value from your load calculation or equipment data.
Air temperature inputEnter ΔT / Enter temperatures
Room temperature · °CUse project/manufacturer data; the example value is editable.
Supply air temperature · °CUse project/manufacturer data; the example value is editable.
Room − supply air temperature difference · KRoom temperature minus supply-air temperature; positive for cooling.
Water temperature inputEnter ΔT / Enter temperatures
Supply water temperature · °CUse project/manufacturer data; the example value is editable.
Return water temperature · °CUse project/manufacturer data; the example value is editable.
Return − supply water temperature difference · KReturn-water minus supply-water temperature for water-side heat transfer.
Air density · kg/m³Air density at design conditions.
Air specific heat · kJ/(kg·K)Air specific heat capacity, used with sensible load.
Mean water temperature · °CMean water temperature used to determine density.
Water specific heat · kJ/(kg·K)Water specific heat capacity; do not assume the same value for glycol.

Steps

  1. Enter total load and select kW, BTU/h or TR.
  2. Enter SHR, air/water temperature differences and fluid properties.
  3. Read results and transfer inputs to duct/pipe sizing; check the receiving tool’s limits.

Worked example

This reproducible training example uses the values below. Select the appropriate mode and overwrite restored project values. Example rates, K values and equipment losses are assumptions, not mandatory design criteria.

All example inputs
ParameterValue / interpretation
Total cooling load10
Capacity unitkW
Sensible heat ratio (SHR)75 %
Air temperature inputEnter ΔT
Room temperature24 °C
Supply air temperature14 °C
Room − supply air temperature difference10 K
Water temperature inputEnter ΔT
Supply water temperature7 °C
Return water temperature12 °C
Return − supply water temperature difference5 K
Air density1.2 kg/m³
Air specific heat1.006 kJ/(kg·K)
Mean water temperature9.5 °C
Water specific heat4.186 kJ/(kg·K)

Expected results (rounded)

ParameterValue / interpretation
Supply airflow2,236.58 m³/h
Chilled-water flow1.72 m³/h

Small differences in displayed rounding are normal. A result that passes the entered limits does not establish suitability for the complete system.

Method & limitations

Simple energy balance; does not simulate coils, dehumidification, bypass or equipment selection.

Supply airflow uses sensible load: V = Q sensible/(ρ·cp·ΔT). Chilled water flow uses total load: V = Q total/(ρ·cp·ΔT).

Supply airflow is not outdoor ventilation airflow. Check dehumidification and coil duty with air states. Pure-water density; no automatic glycol concentration correction.

Room load estimates supply airflow. Coil duty also depends on outdoor air, mixing and additional gains; room load is not automatically coil duty. Use AHU/FAHU for an air-state calculation.

Common mistakes

Using total rather than sensible load for air; zero temperature difference; confusing refrigeration tons with mass tonnes.

Projects & reports

  1. Choose or create an engineering project and enter your actual design inputs.
  2. Project inputs/results are autosaved in this browser. Where a saved-list panel is available, name and add the selected section or alternative to compare multiple options.
  3. Review the report before exporting PDF. In the print dialog select Save as PDF. Export JSON for backup and use Open file to restore it; PDF cannot restore project data.

Saved results do not automatically recalculate when another tool changes. Review any dependency warning, recalculate and update the affected results.

References & related tools

The tool implements the methods and limits stated above; linking a standard does not establish complete compliance with that standard.